Predictive Maintenance Dashboard

Transformer WN-KT8C · live condition monitoring · ← fleet

LIVE · 60s
Overall Risk Score
0 100 50
0
● MEDIUM
Risk Score / 100 · evaluated 2026-06-03 14:10
Score Breakdown & Weighted Formula
35% weight Rule-Based · IEC 90
25% weight DGA Diagnostics 45
20% weight Statistical Z-Score 33
20% weight Isolation Forest 0
Rule-Based · IEC 90 × 0.35 = 31.5
DGA Diagnostics 45 × 0.25 = 11.2
Statistical Z-Score 33 × 0.20 = 6.7
Isolation Forest 0 × 0.20 = 0.0
Score = Rule×0.35 + DGA×0.25 + Stat×0.20 + IF×0.20
= 49.4 → MEDIUM
Action Required
🟡 MEDIUM
Increase monitoring frequency
⏱ within 30 day(s)
NORMAL (0–20)routine
LOW (20–40)schedule
MEDIUM (40–60)inspect ↑
HIGH (60–80)repair 7d
CRITICAL (80+)stop now!
Rule Alerts
1
CRITICAL alerts
0
WARNING alerts
DGA Diagnostics
PD
fault type(s)
45
DGA severity
ML & Statistical
33
Z-Score component
0
Isolation Forest
Overall Assessment
🟡
MEDIUM
act within 30d
Open Alerts (2)
DetectedMethodSeverityMessage
05-02 05:00 rule CRITICAL HYDROGEN-H2 PHASE A (PPM): 760.0 — Partial discharge in oil
05-02 05:00 dga MEDIUM DGA fault PD: Partial discharge (corona)
IEC Rules Catalog (reference)
ParameterUnitWarnCriticalStandard
HYDROGEN-H2 ppm 100 700 IEC 60599
METHANE-CH4 ppm 120 400 IEC 60599
ETHYLENE-C2H4 ppm 50 200 IEC 60599
ACETYLENE-C2H2 ppm 3 35 IEC 60599
CARBON MONOXIDE-CO ppm 350 900 IEEE C57.104
MOISTURE-H2O ppm 10 30 IEC 60422
TOP OIL TEMP °C 85 105 IEC 60076-7
WINDING TEMP °C 98 120 IEC 60076-2
AMBIENT TEMP °C 40 50 IEC 60076-2
OLTC OIL TEMP °C 80 100 IEC 60214-1
BOTTOM OIL TEMP °C 75 95 IEC 60076-7