Transformer WN-KT8C · live condition monitoring · ← fleet
| Detected | Method | Severity | Message |
|---|---|---|---|
| 05-02 05:00 | rule | CRITICAL | HYDROGEN-H2 PHASE A (PPM): 760.0 — Partial discharge in oil |
| 05-02 05:00 | dga | MEDIUM | DGA fault PD: Partial discharge (corona) |
| Parameter | Unit | Warn | Critical | Standard |
|---|---|---|---|---|
| HYDROGEN-H2 | ppm | 100 | 700 | IEC 60599 |
| METHANE-CH4 | ppm | 120 | 400 | IEC 60599 |
| ETHYLENE-C2H4 | ppm | 50 | 200 | IEC 60599 |
| ACETYLENE-C2H2 | ppm | 3 | 35 | IEC 60599 |
| CARBON MONOXIDE-CO | ppm | 350 | 900 | IEEE C57.104 |
| MOISTURE-H2O | ppm | 10 | 30 | IEC 60422 |
| TOP OIL TEMP | °C | 85 | 105 | IEC 60076-7 |
| WINDING TEMP | °C | 98 | 120 | IEC 60076-2 |
| AMBIENT TEMP | °C | 40 | 50 | IEC 60076-2 |
| OLTC OIL TEMP | °C | 80 | 100 | IEC 60214-1 |
| BOTTOM OIL TEMP | °C | 75 | 95 | IEC 60076-7 |